KYN61-40.5(Z) Metalclad AC Enclosed Switchgear, Withdrawable Type

Modle Number: KYN61-40.5(Z)

Product Detail

Product Tags

Product Description

1. General

 

1.1 Ratings: system voltage 40.5kV, rated current up to 2000A, AC 50/60Hz.

 

1.2 Application: applicable for power receiving and distribution of power plant and substations for control, protection and measurement.

 

1.3 Standard: I EC 62271-200

2 Type Designation

3. Main Technical Parameter
   4.1 Switchgear Panel Parameters

ltem Unit Data
Rated voltage kV 40.5 
Rated
current
Rated current of main bus bar A 1250,1600,2000,(2500)
Rated current of matchedVCB A 1250,1600,2000,(2500)
1min power frequency withstand voltage KV 95 
Lightning withstand voltage kV 185 
Power frequency withstands voltage of
auxilarycircuit and control circuit
V/imin  2000 
Rated frequency Hz 50 
Rated short-circuit breaking current kA 202531.5 
Rated short-time withstand current/Rated short-circuit continuous time kA/4s 20  25  31.5
Rated withstands current (peak) kA 50  63  80*
Rated short-circuit making current kA 506380*
Rated voltage of control circuit V DC:110220;
AC:110220
Protection level Switchgear shell
Compartments (door opened)
P3X
P2X


4.2 VCB Parameter

ltem Unit Data
Rated voltage kV 40.5 
Rated current A 1250,1600,2000,(2500)
Rated frequency Hz 50 
Rated short-time breaking current kA 2025  31.5 
Rated short-circuit making current kA 5063  80 
Rated peak withstand current kA 5063  80 
Rated short-time withstand current/Rated short-circuit continuous time kA/4s 2025  31.5 
Rated     1min power frequency withstand voltage (rms) kV 95 
insulation Thundering withstand voltage(rms) KV 185 
evel     Powerfrequency withstand voltage of auxillary circuit and oontrol circuit    V1min 2000 
Mechanical life Times 10000 
Electro-magnetic mechanism s ≤0.2
Making time Spring mechanism S ≤0.15
Breaking time s ≤0.07
Rated operation sequence open-0,3s-closeopen-180s-close