Product Detail

Product Tags

Product Description

ZGS combined transformer, or American transformer, is developed according to the needs of the development of urban and rural power grid construction. It is the large transformer with switchgear, fuse, tap-changer, low-voltage distribution equipment combination on the corresponding auxiliary equipment, can satisfy all kinds of demands of the user electric energy metering, reactive power compensation. ZGS type combined transformer as ac 50 hz, 6 ~ 10 kv network, the rated capacity of 63 ~ 1600 kva independent sets of variable distribution equipment, can be used in outdoor, also can be used for indoor. Widely used in industrial park, urban residential area, commercial center, high-rise buildings and temporary construction site and other places.

 

Technical Parameter:

ZGS11-H(Z)Combined Transformer
Loss (W) Weight (kg) (mm)
Rated
Capacity
Voltage
Group(kV
Connection (75) No-load
current
Impedance (L) (W) (H)
(kVA) HV LV No-load Load % % Machine Oil Gross Dimension
200  10  0.4  Yyn0   or
Dynl1
335  2600  0.6  601  733  1894  1865  1240  1735 
250  390  3050  0.5  716  749  2060  1865  1280  1735 
315  465  3650  0.45  835  733  2148  1865  1730  1735 
400  560  4300  0.4  1006  729  2375  1865  1440  1805 
500  670  5100  0.4  1156  747  2603  1865  1450  1805 
630  840  6200  0.4  4.5  1295  757  2826  1865  1450  1805 
800  980  7500  0.4  1521  872  3357  1450  1495  1805 
000  1190  10300  0.3  1634  970  3704  1865  1510  1805