SG (B) 10 series Non-encapsulated Dry-type Power Transformer

Brand Name: ZHONGHAO

Model Number: SGB10

Phase: Three

Service Voltage: 6-35kV

Rated Capacity: 30-5000kVA

Product Detail

Product Tags

Product Description

SG (B) 10 series of non-encapsulated dry-type power transformers adopt the special process technology of Europe dry-type transformers to ensure that the products fully meet the requirements such as fire prevention, waterproof ,environmental protection. It is the ideal product for distribution systems and widely used in the subway, shipbuilding, mining, chemical, power companies and personnel-intensive buildings as well as other special requirements of the occasion for safety.

Technical Parameter for SG(B)10 Series Non-encapsulated Class H Dry-type Transformer

Product Model No.Connection Group SymbolLoss  WImpedance Voltage(%)No-load Current(%)Overall Dimension (without enclosure)  mmWeight(Kg)
No-load Loss R145℃ Load Loss R(W)LWHL1L2df
SG10-30/10Y,yn0 D,yn11190760429001180880265220550550420
SG10-50/10270107029401180985295220550550450
SG10-80/1037014801.598511801055295226550660740
SG10-100/1040016901.5101011801135295226660660770
SG10-125/1047019801.31060118011753062286608201005
SG10-160/1054022801.31120118012303122286608201015
SG10-200/1062027101.11180123012753122386608201035
SG10-250/1072029601.11290123013303152386608201155
SG10-315/108803730113201340135531524082010701365
SGB10-400/109804280113501340143531524082010701585
SGB10-500/1011605230113951340149532525882010701795
SGB10-630/10134562900.8514501340155032526882010702265
SGB10-630/10130064000.8515451340144532526882010701930
SGB10-800/10152074600.8515901340149033027382010702450
SGB10-1000/10177087600.8516801340155533027682010702640
SGB10-1250/102090103000.8517101470163533528682010703170
SGB10-1600/10245012500  60.85180014701770350330107010703985
SGB10-2000/103050155000.7185014701890350346107010704850
SGB10-2500/103600184000.7190014702030365356107010705620

Notes: The Dimension and weight will be changed according to the requirements. These two data in the table will be subject to the factory documents.