KYN28A-12 (GZS1-12) Model Indoor AC Metal Clad Intermediate Switchgear

Brand Name: ZHONGHAO

Model Number: KYN28

Product Detail

Product Tags

Product Description

1. General

 

1.1 Ratings: system voltage 3.6—12kV, rated current up to 3150A, AC 50/60Hz.

 

1.2 Application: applicable for power receiving and distribution and for control, protection and 

measurement of circuit.

1.3Standards: IEC 62271-200

 

3.Working Condition

3.1 Ambient air temperature: -15°C~~ 40°C (-25°C~~ 45°C available as customized products)

 

3.2 Altitude: W4000m

 

3.3 Relative humidity:

 

Daily average <95%, daily average water vapor pressure <2.2kPa

 

Monthly average W90%, monthly average water vapor pressure W1.8kPa

 

3.4 Earthquake intensity: W magnitude 8

 

3.5 Applicable in places without corrosive, flammable gas and steam and places no regular severe shock. Note: Customized products available.

 

4. Feature

 

3.1 KYN28A-12(Z)(GZS1) and KYN28A-12(Z)(NB) available.

 

3.2 Reliable “anti-5” mechanical latch, convenient and safe maintenance,

 

3.3 Both VCB of ZN63n -12 developed by our company and VD4, VB2 AND 3AH manufactured by other companies around the world can be matched with the switchgear.

5. Main Technical Parameter

Item Unit Data
Rated voltage kV 3.6,72,12
Rated frequency Hz 50 
Ratedcurrent of circuit braker A 630,1250,1600,2000,2500.3150,4000,5000
Ratedcurrent of switchgear A 630,1250,1600,20002500,3150,4000,5000
Rated short time withstand current(4s) kA 16.20.25,31.5,40,50
Ratedwithstand current (peak) kA 40,50,63,80,100,125
Rated short circuitbreaking current kA 16.20.25,31.5,40,50
Ratedshortcircuit closing curent(peak) kA 40,50,63,80,100,125
min power frequency Between poles,pole to earth  kV 24,32,42
H3TPn    withstand voltage Between open contacts kV 24,32,48
nsulation  Lightming  impul etween poles,pole to earth  kV 4,060.75
"vel withstamdvoltage(peak)Between open contacts kV 4,670.85
Protectionleve Shell:IP4X IP2Xwhen theCPT and CB doors are open
     Note:1.The short circuit capacity of the current transformer should be separately considered.
                2.See techmical parameters ofZN63A-12 in relatedcatalogues ofourcompany

6. Structural diagram of switchgear

A、 the bus bar room
B、 the circuit breaker handcart room
C、 the cable room
D、 the relay instrument room
1、 cover
2、 branch small bus bar
3、 bus bar pipe
4、 main bus bar
5、 static contact installation
6、 contact box
7、 current mutual induction
8、 earthed switch
9、 cable
10、 arrester
11、earthed main bus bar
12、 mother board
13、control the small bus bar
14、 earthed switch operating mechanism
15、draw-out horizontal clapboard
16、 heat installation
17、circuit breaker handcart
18、twice connector
19、clapboard (valve )
20、loading and unloading clapboard
21、decompression channel
Product Overview

lt is suitable in a 50Hz 12kV three-phase AC power system, for recieving, distributing, controling, protecting andmonitoring electrical circuit energy.

This product complies with GB3906 "3-35kV AC metal-enclosed switchgear", GB/T11022 "Common technicalreguirements for high-voltage switchgear and control equipment standards", lEC60298"AC metal enclosure switchgearand control equipment with rated voltage above 1kV and 52kV and below", DL/T404"indoor AC high voltage switchgearbooking technical conditions"standard requirements.
Model meaning:

Conditions of use:

Altitude: no more than 1000m;

Ambient temperature: upper limit +40℃, lower limit-15℃(under special process,up to-45 ℃)Relative humidity: daily average <95%,Monthly averages90%;Seismic intensity: Anti-seismic:the seismic intensity does not exceed 8;Environmental conditions: The surrounding air should be free of corrosive or fammable gas.water vapor and other obviousoollution:

No serious pollution and frequent severe vibralion,Slrict design under severe condilions meels Class 1 requiremenls;Jseage under conditions specitied in GB3906 is to be negotiated betwen the user and manufacturer

Project Unit Parameter
Rated voltage                                                              kV 3.6、7.2、12
Rated frequency Hz 50
Circuit breaker rated current                                 A 630、1250、1600、2000、2500、3150
Switch cabinetrated current A 630、1250、1600、2000、2500、3150
Rated dynamic current(4s)                                      kA 16、20、25、31.5、40、50
Rated steady curent(peak) kA 40、50、63、80、100、125
Rated short-circuit breaking current  kA 16、20、25、31.5、40、50
Rated short-circuit closing current(peak)  kA 40、50、63、80、100、125

Rated insulation level
1min
Power frequency withstand voltage
kA 24 32 42

Light impulse withstand voltage
kV 40 60 75
Protection level    IP2Xfor enclosureIP4X,isolation compartment,and cirouit breaker compartment door