Product Detail

Product Tags

Product Description

The YB preinstalled substation is composed of the high-voltage switchgear, low-voltage distribution panel, distribution transformer and enclosure. The high-voltage switchgear adopts air load switch and the transformer is dry-type or oil immersed type. The substation adopts good ventilation structure with elegant appearance and good heat-insulating performance. The temperature rise of the compartments caused by the outdoor solar radiation can be reduced to within the lowest limits on account of the upper and lower ventilation windows. The forced ventilation device and the temperature auto-controlled device should be installed in the substation. The systems of control, protection, live display and the lighting are equipped in each separate unit.

This substation fulfills the functions such as transformation of energy, distribution, transmission, metering, compensation, system control, protection and communication.

Technical Parameter:

No. Items Unit Value
Rated voltage Primary kV 40.5 
Secondary 2;0.69
Subsidiary circuit V 110;220;380
Rated current High voltagecircuit A 400~1250
Low voltage circuit 630~3150
Rated frequency Hz 50 
Rated power kVA 1250;1600;2000~20000
Rated insulation level High voltageside Power frequency 95 
mpact 185 
Low voltage side Power frequency 42 
mpact 75 
Rated short time withstand current High voltageside kA 20;25;31.5
Low voltage side 25;31.5;40
Rated peak withstand current High voltageside 50;63;80
Low voltage side 63;80;100
Insulation level of transformer Power frequency kV 65 
Impact 185 
Insulation level of subsidiary circuit


Product Overview

YB¨-12/0.4 ( F.R ) High and low votage prefabricated substations ( European ) are widely used in urban power gridreconstruction, residential quarters, high-rise bulldings, industrial and mining operations, hotels, shoppingmalls, airports, railways, oil fields, terminals, highways And indoor and outdoor places such as temporary powerfacilities.

This product meets the following standards :

GB/T17467-1998《High voltage/low voltage prefabricated substation 》DL/T537-93 (Technical Conditions for Ordering 6-35kV Box-type Substation》

Model meaning:

Conditions of use:

The altitude does not exceed 2000m:

Ambient temperature:-25℃~+40℃;

Relative humidily: at 25 ℃ , the dally average is not more than 95%, and the monthly average is not more than 90%;installation site: no fire, explosion hazard, conductive dust, chemical corrosive gas and severe vibration. if the aboveonditions are exceeded, the user can consult our company.
Load switch technical conditions:

Project Unit    FKN12-12
   Load switch
FZN25-12
Vaduumload switch
Rated voltage kV 10 
Maximum working voltage       kV                                        12
Rated frequency Hz 50 
Rated current A 630 
Rated breaking load current A 630 
Thermally stable current(effective value) kA/S 20/2 20/4
Dynamic steady current kA 50  50 
Short circuit closing current(peak) kA 50  50 
Full load breaking times 20  10000 
Mechanical lifeimin 2000  10000 
1min
Power frequency withstand voltage(interphase and ground)
kV 42  42 
Lightning impulse voltage(relative to ground) kV                    75 75